What Is the Earth Resistance of a Distribution Transformer

The earth resistance of a distribution transformer is a critical parameter that impacts the safety and performance of the transformer and connected electrical systems. Proper earthing, also known as grounding, ensures effective protection against electric field effects, prevents intermittent discharges, manages potential differences, and shields against magnetic field interference.

voltage transformer

Earth Resistance Requirements

Neutral Point

The neutral point of a transformer is the common point where the phase windings are interconnected. In a three-phase system, the neutral point is typically formed by connecting one end of each phase winding together in a star (wye) configuration. The earth resistance at the neutral point must be low enough to allow fault currents to flow safely to ground without causing dangerous overvoltages.

The specific earth resistance requirements for the neutral point depend on factors such as the transformer rating, system voltage, and grounding method employed. Typical maximum values range from 1-10 ohms, with lower resistances generally required for larger transformers and higher system voltages. Achieving a sufficiently low earth resistance often involves installing multiple ground rods or a ground grid around the transformer.

Equipment Grounding

In addition to the neutral point, all exposed metal parts of the transformer and associated equipment must be securely bonded to earth. This equipment grounding serves several important functions:

  1. It protects personnel from electric shock by providing a low-impedance path for fault currents to flow to ground rather than through a person’s body.
  2. It prevents the buildup of static charges that could lead to discharges or arcing.
  3. It helps equalize potentials between different parts of the system, reducing the risk of dangerous voltage gradients.
  4. It provides a reference point for surge arresters and other protective devices.

As with the neutral point, the earth resistance for equipment grounding must be low enough to safely carry any fault currents that may occur. Typical maximum values are in the range of 5-25 ohms. Multiple ground connections are often used to achieve the required low resistance, especially for large transformers or those located in areas with high soil resistivity.

Purpose of Transformer Earthing

Protection Against Electric Field Effects

One of the primary purposes of earthing a transformer is to protect against the effects of electric fields. The windings and core of a transformer act as a capacitor, storing electric charge. If this charge is allowed to build up, it can cause damaging discharges or flashovers.

Properly designed earthing systems provide a low-impedance path to dissipate any accumulated charges safely to ground. This is especially important for transformers with exposed windings or those located in areas with high levels of airborne contaminants like dust or moisture. By keeping electric fields under control, earthing helps prevent insulation breakdown and extends the life of the transformer.

Prevention of Intermittent Discharges

Another key function of transformer earthing is the prevention of intermittent discharges. These discharges, also known as partial discharges or coronas, occur when the localized electric field intensity exceeds the dielectric strength of the insulating materials. Over time, repeated discharges can degrade insulation, leading to premature failure.

Proper earthing helps prevent intermittent discharges in two ways. First, it limits overall electric field stresses by providing a path for charge dissipation. Second, it establishes a uniform potential reference that minimizes voltage gradients within the transformer. By keeping electric fields below the corona inception level, earthing maintains the integrity of the insulation system.

Management of Potential Differences

Transformer earthing also plays a vital role in managing potential differences within the electrical system. In an ideal situation, all points on a network would be at the same potential. However, in reality, various factors can cause voltages to differ between points. These potential differences can lead to circulating currents, electromagnetic interference, and even dangerous step or touch voltages.

A well-designed earthing system helps manage these potential differences by bonding all exposed conductive parts to a common ground reference. This creates an equipotential zone where voltage gradients are minimized. By eliminating potential differences, earthing enhances both safety and electromagnetic compatibility.

Protection from Magnetic Field Interference

Transformers are also susceptible to magnetic field interference from nearby current-carrying conductors or equipment. This interference can induce circulating currents in the transformer windings, causing additional losses and heating. In extreme cases, magnetic interference can even lead to core saturation and voltage instability.

Earthing provides a degree of protection against magnetic field interference by creating a low-impedance return path for any induced currents. Instead of circulating through the windings, these currents are safely diverted to ground. Effective earthing can thus help reduce losses, prevent overheating, and maintain voltage stability in the presence of external magnetic fields.

Types of Transformer Earthing

Neutral Point Earthing Systems

The method used for earthing the transformer neutral point has a significant impact on the overall performance and protection of the electrical system. There are several common neutral point earthing configurations, each with its own advantages and considerations:

  1. Direct Grounding: In this arrangement, the neutral point is connected directly to earth without any intentional impedance. This provides a low-impedance path for fault currents, effectively limiting overvoltages. However, it can also result in high fault currents that may exceed the interrupting capacity of protective devices.
  2. Reactance Grounding: Here, the neutral point is connected to earth through a current-limiting reactor. This reactance helps reduce fault currents while still providing a ground reference. It is often used in systems where limiting fault currents is necessary to avoid damage to equipment or where continuity of service is critical.
  3. Resistance Grounding: In this case, a resistor is inserted between the neutral point and earth. The resistance value is chosen to limit fault currents to safe levels while still allowing enough current flow for protective relaying. Resistance grounding is commonly used in industrial power systems to minimize arc flash hazards and limit voltage transients.

Ungrounded Systems

In some special applications, the transformer neutral may be left ungrounded or isolated from earth. This is known as an ungrounded or floating neutral system. While ungrounded systems can offer some advantages, such as reduced fault currents and simplified overcurrent protection, they also have significant drawbacks.

Without a ground reference, ungrounded systems are susceptible to high transient overvoltages during line-to-ground faults. These overvoltages can stress insulation and lead to cascading failures if not properly controlled. Ungrounded systems also lack the safety benefits of a grounded neutral, as there is no low-impedance path for fault currents.

Due to these challenges, ungrounded systems are generally limited to specific industrial applications where the benefits outweigh the risks. In most cases, some form of neutral point earthing is recommended to ensure safety, reliability, and equipment protection.

Good!Share this case:
Facebook
LinkedIn
WhatsApp

Contact us for customization

Message Us
Leave A Message

Have any questions? Contact our support team!

Get A Quote