Dry-type Transformer

Additional information

Rated capacity

≤20MVA

Rated primary voltage

≤36kV

Rated secondary voltage

≤1000V

Cooling

AN,ANAF

Vector group

Y/Yn-0, D/Yn-11

Purpose

Three-phase dry power transformers with cast resin and voltage up to 35kV are designed to convert electricity in the networks of power systems and consumers of alternating current electricity of a nominal frequency of 50/60Hz.

  • Application:Indoor
  • Ambient temperature: Maximum temperature: +40℃; Minimum temperature:-30℃
  • Humidity: Monthly average humidity 95%; Daily average humidity 90%
  • Altitude: ≤1000m
  • Max wind speed:35M/s
  • Ambient air not apparently polluted by corrosive and flammable gas, vapor etc.
  • No frequent violent shake

Note: Beyond those services condition, please check with sales before ordering.

0/5 (0 Reviews)
  • Overheat protection and automatic cooling system control
  • Low temperature rise,Low loss & low noise
  • Full testing during production
  • Ecological safety, fire safety, profitability
KVAVoltageTapping
range
LossesNo-load current(%)Weight (KGS)Overall dimension(mm)
H.V.(KV)L.V.(V)No-load(W)Load(W)LWH
50 6
10
11
400
415
433
5 steps
(±2.5%)
27010002.0300630450650
10040015701.3485740630770
12547018501.3550780500700
16054021301.3660840710760
20062025301.1780890710910
25072027601.1880940710850
31588034701.0990990710885
40098039901.012009757101000
500116048801.014251050800920
630130059600.815901170830910
800152069600.818951230850950
1000177081300.8221012608701015
1250209096900.8265013409001050

Note:The above parameters are for reference only.any other requirements,please contact us,thanks.

Online Message

Please fill out the form below, and one of our representatives will get back to you promptly. Your inquiries are important to us, and we strive to provide timely and accurate responses. Thank you for reaching out to ROOQ!

Message Us
Leave A Message